1. SCR power regulator adopts proportional output, harmonic is lower than THID% 5%, and meets the strict requirements of American Power Company IEEE519 (Note: Taiwan Power Company follows the American Electric Power Company specifications).
2. It is required to apply a low harmonic environment to a constant temperature and humidity heating system.
3. The protection device of this controller: (1) The source is out of phase. (2) Fuse disconnection detection. (3) The controller heat sink is over temperature protection. (4) Abnormal output contact, providing remote monitoring use, contact capacity 240VAC/5A.
4. This controller has CE international safety certification standards.
5. With R.S.T each phase fuse disconnection indicator, and provide abnormal output contacts, can be used for system emergency control.
6. The cooling fan action has temperature control, 'When the heat sink temperature is 55oC, it stops at 45oC, which can increase the fan life by 2~3 times.
7. Using low harmonic SCR power regulator, can reduce the amperage of active filter or passive filter, the active filter market price is about 1 amp 5000~8000 yuan, using low harmonic SCR power regulator 1 Ampere is only 1/20 of the price of the active filter.
Main power supply voltage: AC 220V 380~480V ±10%
Auxiliary voltage: AC 220V±15% 50/60Hz
Current Rating: 25A 35A 50A 60A 80A 100A 125A 160A 180A 200A 225A 250A 300A 350A 400A 600A 750A
Working frequency: 47~63Hz
Output method: Proportional output
Input control signals: 4-20mA, 0-5V, 1-5V, 0-10V, 2-10V.
Output voltage range: 0~100%
Operating environment: -10°C~50°C Humidity 90%RH or less
Insulation resistance: 20 MΩ or more (between power supply and case), 20 MΩ or more (between input signal and case)
Compressive strength: between the power supply and the enclosure 2500VAC / 1 minute, power and input signal 1000VAC / 1 minute
JK3826S1/JK3842S1/JK3856S1/JK3872S1
JK2226SF/JK2242SF/JK2256SF/JK2272SF
JK3826SF/JK3842SF/JK3856SF/JK3872SF